Based on the constant power method & engineering empirical formula, supports ageing coefficients, discharge depth, temperature correction, accurate estimation of capacity requirements for lead acid batteries and configuration options
Design reference for YD/T 5040 / IEEE 485
⁇ Total load powerkW (power)
♪ Back-up time ♪min
Battery voltageV DC
⁇ Inverse efficiency%
⁇ Exploited depth (DOD)0.6~0.8
An ageing factor1.2~1.4
⁇ Temperature compensation factor≥1.0
⁇ Single cell voltageV (commonly used 12V)
⁇ Select single-body capacity reference (Ah)Suggested number of combinations
⁇ Description of formulae for calculation
Total required capacity (Ah) = [P_load(kW)x T(h)x1000] / [V_bat(V)x ⁇ inv x DOD] x K_aging x K_temp]
⁇ and combined = ceil (Ah/ Single Ah) ⁇ Serial = cil (V_bat/ Single voltage) Ageing, temperature factors ensure long-term reliability and are consistent with IDC design redundancy.
0.0 Ah
Total battery capacity for theory
Total configuration capacity (actual)0 Ah
Number of strings (each)- Section
⁇ Number of combinations (recommended)- Group
⁇ Total battery sections- Section
⁇ Direct stream side demand power0 kW
⁇ Total energy requirements (Wh)0 Wh
• Engineering proposals
• Normally, IDC recommends discharge depths DOD ~ 0.8, and the aging factor of 1.25 can guarantee the discharge requirements at the end of the design life.
• The actual selection recommendation is based on the plant's constant power discharge table, and this calculator provides accurate estimates and recommendations for the number of groups.
• If the lead time is > 60 minutes, it is recommended that redundancy be added or that the capacity factor be combined or increased.
:: The results of the calculation are based on an engineering empirical formula, which combines data centre standards and the final configuration is confirmed in conjunction with a battery discharge curve.
How to use
Enter the UPS load, DC voltage, battery capacity and other requested parameters.
Adjust the presets for your equipment and review the capacity and runtime estimates.
Check the battery configuration and efficiency assumptions. Final selection should use the manufacturer's discharge curves and your design requirements.