IDC machine room . UPS battery capacity calculator

Based on the constant power method & engineering empirical formula, supports ageing coefficients, discharge depth, temperature correction, accurate estimation of capacity requirements for lead acid batteries and configuration options

Design reference for YD/T 5040 / IEEE 485
⁇ Total load power kW (power)
♪ Back-up time ♪ min
Battery voltage V DC
⁇ Inverse efficiency %
⁇ Exploited depth (DOD) 0.6~0.8
An ageing factor 1.2~1.4
⁇ Temperature compensation factor ≥1.0
⁇ Single cell voltage V (commonly used 12V)
⁇ Select single-body capacity reference (Ah) Suggested number of combinations
⁇ Description of formulae for calculation
Total required capacity (Ah) = [P_load(kW)x T(h)x1000] / [V_bat(V)x ⁇ inv x DOD] x K_aging x K_temp]
⁇ and combined = ceil (Ah/ Single Ah) ⁇ Serial = cil (V_bat/ Single voltage)
Ageing, temperature factors ensure long-term reliability and are consistent with IDC design redundancy.
0.0 Ah
Total battery capacity for theory
Total configuration capacity (actual) 0 Ah
Number of strings (each) - Section
⁇ Number of combinations (recommended) - Group
⁇ Total battery sections - Section
⁇ Direct stream side demand power 0 kW
⁇ Total energy requirements (Wh) 0 Wh
• Engineering proposals
• Normally, IDC recommends discharge depths DOD ~ 0.8, and the aging factor of 1.25 can guarantee the discharge requirements at the end of the design life.
• The actual selection recommendation is based on the plant's constant power discharge table, and this calculator provides accurate estimates and recommendations for the number of groups.
• If the lead time is > 60 minutes, it is recommended that redundancy be added or that the capacity factor be combined or increased.
:: The results of the calculation are based on an engineering empirical formula, which combines data centre standards and the final configuration is confirmed in conjunction with a battery discharge curve.